Updates since revision 3.8 Revision 3.8 S10 ---------------- * Fixed: The Modbus TCP connexion timeout must take into account the Modbus Rx/TX timeout parameter. Revision 3.8 S9 --------------- * CRITICAL FIX: When accessing the web site or accessing file, or in many other situation, there could have illegal memory access, typicaly the events files reported an error like. 04/12/1999 19:09:24 22904 Reboot reason: Illegal memory access (0xC312C) wd The problem appeared rarely but it did appear. Another symptom was when accessing files from the FTP server and/or from export bloc descriptors and/or from the web site at the same time, the result could generate a file mixing informations of different files. * Changed: UNITE driver can work on RS232 link (new configuration option). * SMS Syntax update The following protocols are supported (no change), tap, ucp, gsm, ifz. It is possible to add a word datasize and parity specification: examples: tap7o, tap7e, tap7n, tap8n This can be done for "tap" and "ucp" The generic syntax is tapDP or ucpDP with Datasize D= 8 or 7 with Parity P= n: none, o: odd, e: even BENELUX SEMASCRIPT ------------------ Possibility to send Semascript/ SemaDigit to BENELUX Semaphone using the Belgacom server: Sending a semadigit to 0498373101 you must call the server at phone number 0458500001 (0+0458500001 if you must first dial a 0 on a PABX) keep only the last 7 digits of the semaphone and use TAP protocol with 7e1 sendsms "8373101,tap7e1,0458500001","023891131" if the eWON is behind a PABX and 0 must be dialed first use: sendsms "8378101,tap7e1,0+0458500001","023891131" Revision 3.8 S8 --------------- - Incorrect response when routing XIP to unitelway to another unitelway slave Revision 3.8 S7 --------------- - Don't care about dst_idx byte in XIP frames for compatibility with Applicom driver. - Bugfix: Counter did not work on DI1 input. Revision 3.8 S6 --------------- Bug fix: - When Modbus is disabled the eWON reboots continuously. This bug was introduced in release S5 Revision 3.8 S5 --------------- - Fixed problem when using modbus gateway on multiple slaves - Added modbus advanced param USecReqDelay. This is a number of microseconds the eWON waits after a message is sent. The eWON will always wait at least 4 chars before sending another request to the bus. If this time is longer than the time for sending 4 chars (at the programmed baudrate), then USecReqDelay is used, otherwise the 4 chars computed value is used. Defaults to 0 REM: currently this delay may be actually limited to 20000 uSec - Modbus: When a gateway request is received for address 0, the address is replaced by 1 and message is forwarded to the serial modbus slave (with address 1). REM: the address is not substitued back when response is forwarded in return. - Fixed Full reset problem: the hardware test result was not displayed, eWON was immediately rebooting - Fixed: SMS text problem: some characters were replaced by the letter 'u' Revision 3.8 S4 --------------- Bug Fix: - With some ISP providers the ACCM was not negociated correctly resulting in unstable PPP connection when the eWON connected to the server. This problem has currently only been observed with GSM-GPRS providers. New: - If mail content starts with